LV Circuit Breaker Sizing & Verification — AC ≤ 1 kV — IEC 60364-4-43:2023 / IEC 60947-2
Circuit and load
IB and Iz are final project inputs. Use the Cable Sizing tool for derating. Parallel conductors and neutral/earth-fault protection require separate assessment.
Breaker and prospective fault
Ue is the operational voltage, not insulation voltage Ui. Icu and Ics must apply to the entered system voltage and frequency; do not reuse a higher capacity from a lower voltage. I2 is an absolute operating current, not a generic multiplier.
Cable short-circuit withstand
For current-limiting breakers or clearing below 0.1 s, use manufacturer's total let-through energy, including the complete breaking interval. Enter its worst value over the relevant fault-current range.
Minimum fault and making capacity
Use the upper pickup bound, including tolerance. Pickup alone does not prove disconnection time. The time limit is a project input; this tool does not determine IEC 60364-4-41 shock-protection requirements.
Verification result
Report package
Compact Word report contains the inputs, method, calculation summary, results, verdict and limits. Full report adds detailed derivation, a data register, glossary and verification examples.
Method, references and limits
IEC 60364-4-43:2023: 431.4.2 overload coordination; 431.5.4 short-circuit protection and Table 2 conductor factors. Schneider Electric Electrical Installation Guide: engineering explanation of the overload and thermal conditions. IEC 60947-2 manufacturer ratings are entered by the engineer; product certification is not assessed here.
Glossary
Built-in validation tests — expand
Independent hand-worked examples applying the IEC equations, not a claim that these numerical examples are printed in the standard. The factor test separately pins the 1.45 coordination coefficient. Sample k=143 is an explicit project input.